Product Description
Key Features
- Exact product identity: SIMATIC DP electronic module for ET 200SP; product type designation: F-AI 4xI 0(4)..20mA 2-/4-wire HF.
- Fail-safe analog inputs: 4 analog inputs for current measurement with 0 to 20 mA and 4 mA to 20 mA input ranges.
- Supply and encoder output: 24 V rated supply; encoder supply is 24 V with short-circuit protection and 300 mA maximum total current of all encoders/channels.
- Signal processing: 16 bit maximum resolution with overrange including sign; parameterizable integration time and 7 smoothing levels.
- Diagnostics and interfaces: Wire-break, short-circuit, supply-voltage monitoring, diagnostic alarm, RUN/ERROR/PWR/channel-status LEDs, and I&M0 to I&M3 data.
- Safety and mounting data: Up to PLe and Cat. 4 according to ISO 13849-1 and SIL 3 according to IEC 61508; dimensions are 15 mm × 73 mm × 58 mm.
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Product type designation | F-AI 4xI 0(4)..20mA 2-/4-wire HF |
| Analog inputs | 4 |
| Input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Rated supply voltage | 24 V DC |
| Resolution with overrange | 16 bit |
| Firmware update possible | Yes |
| Engineering | STEP 7 TIA Portal configurable/integrated from V15 with HSP 203 |
| Safety level | PLe, Cat. 4 according to ISO 13849-1; SIL 3 according to IEC 61508 |
Frequently Asked Questions
What exact order number should be confirmed for this Siemens module?
Confirm the nameplate order number 6ES7136-6AA00-0CA1 and the product type designation F-AI 4xI 0(4)..20mA 2-/4-wire HF.
Which input ranges and channel count does 6ES7136-6AA00-0CA1 have?
It has 4 current-measurement inputs with 0 to 20 mA and 4 mA to 20 mA input ranges.
Which firmware and engineering details should be checked?
FW update is possible, and configuration/integration with STEP 7 TIA Portal is supported from V15 with HSP 203.
What supply and mounting details should be confirmed?
Confirm the 24 V rated supply, dimensions of 15 mm × 73 mm × 58 mm, and the required installation orientation and temperature limits.