Product Description
Key Features
- Exact product identity: Product type designation: IM 155-6 DP HF. The bundle includes interface module 6ES7155-6BU01-0CN0, server module 6ES7193-6PA00-0AA0 and PROFIBUS plug 6ES7972-0BB70-0XA0.
- Module capacity: Supports up to 32 operable ET 200SP modules and 16 operable ET 200AL modules.
- PROFIBUS interface: Has 1 integrated RS 485 socket and supports PROFIBUS DP device, PROFIBUS, PROFIsafe, SYNC, FREEZE, DPV0 and DPV1. Transmission rate: max. 12 Mbit/s.
- Firmware and engineering: Firmware version: V4.2; FW update possible: Yes. STEP 7 TIA Portal is configurable/integrated from V15 SP1. STEP 7 is configurable/integrated from V5.5 SP4 only up to FW V3.1.
- Supply and protection: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity protection and short-circuit protection: Yes.
- Installation and dimensions: Dimensions: 50 mm width, 117 mm height and 74 mm depth; weight approx. 150 g. Operating temperature is -25 °C to 60 °C for horizontal installation and -25 °C to 50 °C for vertical installation, with no condensation.
Technical Summary
| Product type designation | IM 155-6 DP HF |
|---|---|
| Product lifecycle | Active Product |
| Firmware version | V4.2 |
| Module swapping during operation | Yes; Multi-hot swapping |
| Quantity of operable ET 200SP modules, max. | 32 |
| Quantity of operable ET 200AL modules, max. | 16 |
| Number of PROFIBUS interfaces | 1 |
| Transmission rate, max. | 12 Mbit/s |
| Rated supply voltage (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| product phase-out | planned – see SIOS 109989704 |
Frequently Asked Questions
What order number should be confirmed for this Siemens module?
Confirm the complete order number 6ES7155-6BA01-0CN0 and the product type designation IM 155-6 DP HF.
Which firmware version does the module have?
The firmware version is V4.2, and FW update possible is Yes.
How many modules can the configuration support?
It supports up to 32 operable ET 200SP modules and 16 operable ET 200AL modules.
Which interface and connector configuration should be checked?
The module has 1 integrated RS 485 socket, and the bundle includes PROFIBUS plug 6ES7972-0BB70-0XA0.
What lifecycle information should be confirmed for an inquiry?
The product lifecycle is Active Product; product phase-out is planned – see SIOS 109989704.