Product Description
Key Features
- Exact BaseUnit identity: SIMATIC ET 200SP BaseUnit BU15-P16+A0+2B, BU type A0, with bridged connection to the left.
- Push-in terminal configuration: Has Push-in terminals, 16 process terminals to the I/O module, and 2 terminals with connection to the P1 and P2 bus.
- Supply and current capacity: Rated supply voltage: 24 V DC. Current carrying capacity: max. 10 A for the P1 and P2 bus and max. 2 A for process terminals.
- AUX terminal exclusion: Without AUX terminals; the number of terminals to the AUX bus is 0.
- Installation and dimensions: Width: 15 mm; height: 117 mm; depth: 35 mm. Horizontal installation ambient temperature: -30 °C to 60 °C; vertical installation: -30 °C to 50 °C.
- Protection and lifecycle data: External protection for power supply lines: 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic. Product lifecycle: Active Product.
Technical Summary
| Product type | BU type A0 |
|---|---|
| Product lifecycle | Active Product |
| Configuration | BU15-P16+A0+2B; bridged to the left |
| Rated supply voltage | 24 V DC |
| P1 and P2 bus current carrying capacity, max. | 10 A |
| Process terminal current carrying capacity, max. | 2 A |
| Terminals | Push-in terminal; 16 process terminals; 2 terminals to P1 and P2 bus |
| AUX terminals | 0; without AUX terminals |
| Horizontal installation ambient temperature | -30 °C to 60 °C |
| Vertical installation ambient temperature | -30 °C to 50 °C |
Frequently Asked Questions
What exact order number should be confirmed for this BaseUnit?
Confirm Siemens order number 6ES7193-6BP00-0BA0 and the configuration BU15-P16+A0+2B.
What terminal type does the 6ES7193-6BP00-0BA0 use?
It has Push-in terminals, including 16 process terminals to the I/O module and 2 terminals connected to the P1 and P2 bus.
Does this configuration include AUX terminals?
It is without AUX terminals. The number of terminals to the AUX bus is 0.
What supply and external line protection are specified?
The rated supply voltage is 24 V DC. External protection is a 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic.