Product Description
Key Features
- Controller identity and lifecycle: CPU 1507D TF based on SIMATIC S7-1500 TF-CPU and SINAMICS S120; lifecycle: Active Product.
- Digital I/O capacity: 28 integrated digital input channels and 16 integrated digital output channels, with parameterizable input and output functions.
- Drive control capacity: Maximum 6 axes for servo control, 6 axes for vector control and 12 axes for V/f control.
- Interfaces: 3 PROFINET interfaces, 1 PROFIBUS interface and 4 DRIVE-CLiQ interfaces. A SIMATIC Memory Card is required.
- Firmware and engineering: PLC firmware up to V3.1 and SINAMICS Integrated firmware V5.2 SP3; configurable or integrated with STEP 7 TIA Portal V21 (FW V3.1) / V16 (FW V2.8) or higher.
- Supply and installation: Rated supply voltage: 24 V DC; permissible range: 20.4 V to 28.8 V DC. Protection degree: IP20 for control cabinet installation / open type.
Applications
- Integrated drive control: Supports servo, vector and V/f control for integrated drive axes.
- PROFINET communication: Supports PROFINET IO Controller and PROFINET IO device functions.
- Digital signal processing: Supports parameterizable digital inputs and outputs, counters, probes, time stamps, PWM and oversampling.
Technical Summary
| Product type | CPU 1507D TF |
|---|---|
| Product lifecycle | Active Product |
| Digital inputs | 28 integrated channels |
| Digital outputs | 16 integrated channels |
| Drive control | 6 servo axes max.; 6 vector-control axes max.; 12 V/f-control axes max. |
| Interfaces | 3 PROFINET; 1 PROFIBUS; 4 DRIVE-CLiQ |
| Supply voltage | 24 V DC rated; 20.4 V to 28.8 V DC permissible |
| Firmware | PLC up to V3.1; SINAMICS Integrated V5.2 SP3 |
| Memory card | SIMATIC Memory Card required |
| Protection | IP20 control cabinet installation / open type |
Frequently Asked Questions
What order number should be confirmed for this controller?
Confirm the complete nameplate order number: 6ES7615-7DF10-0AB0.
Which firmware versions are supported?
Supported firmware is PLC up to V3.1 and SINAMICS Integrated V5.2 SP3. The collected data also states SINAMICS FW V5.2/V5.2 SP3.
What I/O and interface configuration should be checked?
Check the configuration of 28 integrated digital input channels, 16 integrated digital output channels, 3 PROFINET interfaces, 1 PROFIBUS interface and 4 DRIVE-CLiQ interfaces.
Is a memory card included in the configuration?
A SIMATIC Memory Card is required; the source does not state that one is included.