Product Description
Key Features
- Exact SIPLUS CPU identity: Product type: CPU 1214C AC/DC/relay; based on 6ES7214-1BG40-0XB0, with conformal coating.
- Integrated I/O: 14 digital inputs at 24 V DC, 10 relay digital outputs with 2 A maximum resistive load, and 2 analog inputs with 0 to +10 V input range.
- AC power supply: Supply range: 85 V AC to 264 V AC at 47 Hz to 63 Hz; rated values include 120 V AC and 230 V AC.
- PROFINET interface: 1 isolated PROFINET interface with 1 RJ 45 port and transmission rate up to 100 Mbit/s.
- Firmware and memory: Firmware version: V4.1; integrated work memory: 100 kbyte; integrated load memory: 4 Mbyte.
- Environmental specification: Ambient temperature during operation: -40 °C to 70 °C; start-up at -25 °C; IP20 protection.
Applications
- Counter functions: Supports high-speed counting with 6 digital inputs usable for technological functions and counting frequency up to 100 kHz.
- Controlled positioning: Supports controlled positioning and up to 8 position-controlled positioning axes.
- PID control: Includes a PID controller.
Technical Summary
| Product type | CPU 1214C AC/DC/relay |
|---|---|
| Product lifecycle | Active Product |
| Digital inputs | 14; 24 V DC |
| Digital outputs | 10; relays; 2 A maximum with resistive load |
| Analog inputs | 2; 0 to +10 V |
| Power supply | 85 V AC to 264 V AC; 47 Hz to 63 Hz |
| PROFINET interfaces | 1; isolated; RJ 45; up to 100 Mbit/s |
| Firmware version | V4.1 |
| Memory | 100 kbyte work memory; 4 Mbyte load memory |
| Protection | IP20 |
Frequently Asked Questions
What exact firmware version should be confirmed for Siemens 6AG1214-1BG40-2XB0?
The supplied firmware version is V4.1; confirm the required version against the installed part.
Which interfaces should be checked for this CPU?
It has 1 isolated PROFINET interface with 1 RJ 45 port; confirm the installed connection requirements.
What mounting dimensions should be checked?
The dimensions are 110 mm width, 100 mm height and 75 mm depth; confirm the available installation space.
What configuration does this order number include?
It has 14 digital inputs, 10 relay digital outputs and 2 analog inputs. The configuration has 0 signal boards; confirm the installed configuration.