Product Description
Key Features
- Product identity: SIPLUS S7-300 FM350-1 based on 6ES7350-1AH03-0AE0, with conformal coating.
- Counter capacity: 1 counter input with 32 bit or ±31 bit; counting frequency up to 500 kHz for 5 V input and up to 200 kHz for 24 V input.
- Encoder connections: Supports symmetrical and asymmetrical incremental encoders, 24 V initiators, and 24 V directional elements.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 20.4 V to 28.8 V, with dynamic limits of 18.5 V and 30.2 V.
- Digital I/O: 3 digital inputs and 2 digital outputs; the outputs have electronic short-circuit protection.
- Product lifecycle: Product cancellation.
Applications
- Counter functions: Provides counter functions for connection of 5 V and 24 V incremental encoders.
Technical Summary
| Product model | 6AG1350-1AH03-2AY0 |
|---|---|
| Product family | SIPLUS S7-300 FM350-1 |
| Counter inputs | 1; 32 bit or ±31 bit |
| Counting frequency, max. | 500 kHz for counter input 5 V; 200 kHz for counter input 24 V |
| Rated supply voltage | 24 V DC |
| Encoder supply | 5.2 V ±2 %; 1L+ (-3 V) |
| Digital inputs / outputs | 3 / 2 |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What counter capacity does 6AG1350-1AH03-2AY0 have?
It has 1 counter input with 32 bit or ±31 bit.
What encoder input frequencies are supported?
The maximum counting frequency is 500 kHz for the 5 V counter input and 200 kHz for the 24 V counter input.
Which encoder types can be connected?
It supports symmetrical and asymmetrical incremental encoders, 24 V initiators, and 24 V directional elements.
What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V and dynamic limits of 18.5 V and 30.2 V.