Product Description
Key Features
- Exact model and lifecycle: Siemens 6SL3210-1KE11-8AB2, SINAMICS G120C; Active Product.
- Rated input and output: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output rated power: 0.55 kW LO or 0.37 kW HO.
- Overload ratings: LO: 150% for 3s, 110% for 57s, 100% for 240s. HO: 200% for 3s, 150% for 57s, 100% for 240s.
- I/O and safety: 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input and 1 non-isolated analog output. Safe Torque Off is integrated.
- Communication and connections: Fieldbus: USS/MODBUS RTU. Line side, motor end and DC link use plug-in screw terminals; PE connection is on the housing with M4 screw.
- Installation and protection: Frame size: FSAA. Protection: IP20 / UL open type. Width: 73 mm; depth: 155 mm. Cooling uses an integrated fan.
Technical Summary
| Product | Siemens 6SL3210-1KE11-8AB2 SINAMICS G120C |
|---|---|
| Lifecycle | Active Product |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power (LO) | 0.55 kW | 0.75 hp |
| Rated power (HO) | 0.37 kW | 0.50 hp |
| Fieldbus | USS/MODBUS RTU |
| I/O | 6DI, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input, 1 non-isolated analog output |
| Safe Torque Off | Integrated |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
| Connections | Plug-in screw terminals; PE connection on housing with M4 screw |
Frequently Asked Questions
What exact model should be confirmed for this SINAMICS G120C unit?
Confirm the complete order number: 6SL3210-1KE11-8AB2.
What are the input and output ratings?
Input is 3 AC, 380 … 480 V +10 % -20 % at 47 … 63 Hz. Rated output power is 0.55 kW LO or 0.37 kW HO.
Which communication interface is supplied?
The fieldbus is USS/MODBUS RTU.
What I/O and safety configuration does it have?
It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input, 1 non-isolated analog output and integrated Safe Torque Off.