Product Description
Key Features
- Digital output configuration: 8 parameterizable source outputs (PNP, current-sourcing), with 0.5 A rated output current per channel.
- Supply and output ratings: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Output voltage is rated at 24 V DC.
- SIMATIC ET 200SP identity: Product type designation: DQ 8x24VDC/0.5A ST. The module fits BU type A0 and has color code CC02.
- Firmware and engineering: Firmware version is V0.0, with no firmware update possible. STEP 7 TIA V14 with HSP0222 and TIA V15 are supported for configuration or integration.
- Output protection and diagnostics: Electronic short-circuit protection, open-circuit detection, supply-voltage monitoring, wire-break and short-circuit diagnostics, and substitute values are supported.
- Installation and isolation: Mechanical coding element Type A and automatic encoding are provided. Channels are isolated from the backplane bus but not from each other or load voltage L+.
Applications
- Digital input control: The module supports controlling a digital input.
Technical Summary
| Product type | DQ 8x24VDC/0.5A ST |
|---|---|
| Digital outputs | 8 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Output current per channel | 0.5 A |
| Maximum current per module | 4 A |
| BaseUnit | BU type A0 |
| Firmware version | V0.0 |
| PROFINET GSDML | V2.3 |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact order number of this Siemens module?
The exact order number is 6ES7132-6BF01-0BA0.
How many outputs does the module have?
It has 8 parameterizable source outputs (PNP, current-sourcing), with 0.5 A rated current per channel.
Which BaseUnit does this module use?
It fits BU type A0.
What firmware version is supplied, and can it be updated?
The firmware version is V0.0, and firmware updating is not possible.
Which diagnostics are supported?
It supports supply-voltage monitoring, module-wise wire-break and short-circuit diagnostics to ground and L+, group error indication, and substitute values.