Siemens Industrial Automation

6SL3210-1KE31-1UF1

Siemens 6SL3210-1KE31-1UF1 SINAMICS G120C with 380-480 V 3 AC input, 55.00 kW rated power (LO), PROFINET, IP20 and integrated Safe Torque Off. Check a legacy-part verification inquiry.

Complete Product Information
Product Code
6SL3210-1KE31-1UF1
Dimensions
59.5 × 40 × 35 cm
Weight
27 kg
Lifecycle
Active Product
Availability
Check availability with quotation
Lead Time
Confirmed with quotation
Product Attachment
Download technical file

Availability, lead time, condition and warranty are confirmed for each quotation.

Product Information

Technical Product Information

Product Description

Key Features

  • Rated power and input: Rated power: 55.00 kW (LO) or 45.00 kW (HO). Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz.
  • Interfaces and safety: Communication: PROFINET, EtherNet/IP. Safe Torque Off is integrated.
  • I/O configuration: The unit has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.
  • Control modes: It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
  • Connections and cooling: Line-side and motor-end connections use screw-type terminals. Cooling is air cooling using an integrated fan.
  • Protection and physical variant: Degree of protection: IP20 / UL open type. Frame size: FSE. Dimensions: 275 mm width and 237 mm depth. Net weight: 26.50 kg.

Technical Summary

Product Siemens 6SL3210-1KE31-1UF1
Product family SINAMICS G120C
Rated power (LO) 55.00 kW | 60.00 hp
Rated power (HO) 45.00 kW | 50.00 hp
Input 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz
Communication PROFINET, EtherNet/IP
Safe Torque Off Integrated
Output frequency for vector control 0 … 240 Hz
Output frequency for V/f control 0 … 550 Hz
Degree of protection IP20 / UL open type
Frame size FSE

Frequently Asked Questions

What input ratings should be confirmed for 6SL3210-1KE31-1UF1?

Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Rated current is 96.00 A (LO) or 85.00 A (HO).

Which communication interfaces and safety function does it have?

Communication: PROFINET and EtherNet/IP. Safe Torque Off is integrated.

What I/O configuration should be matched?

It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.

What mounting and protection details should be checked?

Frame size: FSE. Protection: IP20 / UL open type. Width: 275 mm; depth: 237 mm; net weight: 26.50 kg.

Product Information

RFQ Information

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

01Which product reference should I send?

Send the complete model, order number or MLFB shown on the product. Include the hardware version when it matters.

02How are supply terms confirmed?

Availability, condition, lead time, warranty and delivery terms are stated for the specific quotation.

03What helps with replacement requests?

Share the installed model, application, electrical and mechanical requirements, communication interface and a clear nameplate photo.

Product RFQ

Send the Details Needed for a Quotation

Use the form for the product model, quantity and contact details. Add the destination and technical questions in the message.

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

Email Your Requirement

* Email is required. Other fields are optional, but more detail helps us respond accurately.

Request a Quote