Product Description
Key Features
- Exact model and base: 6AG1322-1FH00-7AA0, based on 6ES7322-1FH00-0AA0.
- Digital outputs: 16 isolated digital outputs with potential separation in groups of 8.
- Load voltage: Rated load voltage: 230 V; 120/230 V AC. Permissible range: 79 V to 264 V.
- Output current: Rated output current for signal "1": 1 A. For 0 to 40 °C, the permissible range is 10 mA to 1 A; for 40 to 60 °C, 10 mA to 0.5 A.
- Protection and diagnostics: Short-circuit protection has an 8 A, 250 V fuse per group. Diagnostics indicate a blown fuse; a Fuse OK FSG green LED, red fuse LED, Group error SF red LED and digital-output status indicator are provided.
- Environmental and lifecycle data: Conformal coating; -40…+70 °C. Product cancellation.
Applications
- Digital input control: The digital outputs can control a digital input.
Technical Summary
| Product model | 6AG1322-1FH00-7AA0 |
|---|---|
| Base model | 6ES7322-1FH00-0AA0 |
| Digital outputs | 16 |
| Rated load voltage | 230 V; 120/230 V AC |
| Permissible load-voltage range | 79 V to 264 V |
| Rated output current | 1 A |
| Output-current range, 0 to 40 °C | 10 mA to 1 A |
| Output-current range, 40 to 60 °C | 10 mA to 0.5 A |
| Potential separation | In groups of 8; between channels and backplane bus by optocoupler |
| Isolation test | 4 000 V DC |
| Lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact Siemens model and base model?
The exact model is 6AG1322-1FH00-7AA0, based on 6ES7322-1FH00-0AA0.
What load voltage and output current does this module have?
Rated load voltage is 230 V; 120/230 V AC. Rated output current for signal "1" is 1 A. From 0 to 40 °C, the permissible output-current range is 10 mA to 1 A; from 40 to 60 °C, it is 10 mA to 0.5 A.
How are the digital outputs separated?
The 16 digital outputs have potential separation in groups of 8. Separation between the channels and backplane bus uses an optocoupler.
Does the module include short-circuit protection and diagnostics?
It has an 8 A, 250 V fuse per group and diagnostics for a blown fuse. Short-circuit and wire-break diagnoses are not provided.