Product Description
Key Features
- Exact controller identity: SIMATIC DP IM151-7 F-CPU for ET200S, with integrated PROFIBUS DP interface and 9-pole D-sub socket as DP Slave.
- Memory configuration: Integrated work memory: 192 kbyte. The work memory is not expandable; plug-in MMC load memory is supported up to 8 Mbyte.
- Supply and protection: Rated DC supply: 24 V, permissible range 19.2 V to 28.8 V. Reverse polarity protection is provided against destruction.
- Interface and communication: Integrated RS 485 interface with PROFIBUS DP device support, active / passive operation, and transmission rate up to 12 Mbit/s.
- Firmware and lifecycle: Firmware version: V3.3. Product lifecycle: Product cancellation. The configuration is without battery; SIMATIC MMC is required.
Technical Summary
| Product identity | SIMATIC DP IM151-7 F-CPU for ET200S |
|---|---|
| Work memory | 192 kbyte, integrated; not expandable |
| Load memory | Plug-in MMC, max. 8 Mbyte |
| Supply voltage | 24 V rated DC; 19.2 V to 28.8 V permissible range |
| PROFIBUS DP interface | Integrated RS 485 interface; DP device, active / passive |
| PROFIBUS DP transmission rate | Max. 12 Mbit/s |
| Interface connector | 9-pole D-sub socket |
| Firmware version | V3.3 |
| Mounting rail | 1 mounting rail; station width ≤ 1 m or < 2 m |
| Product lifecycle | Product cancellation |
| Configuration exclusions | Without battery; SIMATIC MMC required |
Frequently Asked Questions
Which exact order number should be confirmed for this legacy part?
Confirm 6ES7151-7FA21-0AB0 on the nameplate or installed-part documentation.
What firmware version does this controller have?
Firmware version: V3.3.
Which interface and connector should be checked?
It has an integrated PROFIBUS DP interface through an RS 485 interface with a 9-pole D-sub socket; transmission rate is up to 12 Mbit/s.
What memory configuration should be verified?
It has 192 kbyte integrated, non-expandable work memory and plug-in MMC load memory up to 8 Mbyte.
Is the selected configuration supplied with a battery?
It is without battery; SIMATIC MMC is required.