Product Description
Key Features
- Product configuration: SIPLUS G120 PM240-2 IP20-FSF-U-400V, FSF design, based on 6SL3210-1PE32-5UL0, with conformal coating.
- Power and overload ratings: Low overload: 132 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s. High overload: 110 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s.
- Supply and braking: 380-480 V 3 AC +10/-20%, 47-63 Hz, unfiltered, with an integrated braking chopper.
- Output and pulse frequency: Maximum output current: 410 A; output current without overload: 250 A; pulse frequency: 2 kHz.
- Protection and installation: IP20 protection; dimensions are 708x 305x 357 (HxWxD). The unit is supplied without CU and operating unit.
- Lifecycle and firmware: Lifecycle status: Active Product. Released as of CU FW version V4.7 HF8.
Technical Summary
| Product name | 6AG1210-1PE32-2UL0 |
|---|---|
| Product type | PM240-2 |
| Product version | FSF 132 kW |
| Low overload power | 132 kW |
| High overload power | 110 kW |
| Input voltage | 380-480 V 3 AC +10/-20% |
| Frequency | 47-63 Hz |
| Maximum output current | 410 A |
| Pulse frequency | 2 kHz |
| Degree of protection | IP20 |
| Lifecycle status | Active Product |
Frequently Asked Questions
What power ratings should be confirmed for the 6AG1210-1PE32-2UL0?
Low overload is 132 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s. High overload is 110 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s.
What supply is specified for this SIPLUS drive?
The supply is 380-480 V 3 AC +10/-20% at 47-63 Hz. The unit is unfiltered and has an integrated braking chopper.
What is included in the specified configuration?
The unit is without CU and operating unit. It has IP20 protection and FSF design.
Which firmware release point is supplied for verification?
The product is released as of CU FW version V4.7 HF8.