Product Description
Key Features
- Exact product identity: SIPLUS ET 200SP F-AI 4xI 0(4)..20mA 2-/4-wire HF module, based on 6ES7136-6AA00-0CA1.
- Analog input capacity: 4 analog inputs for current measurement, supporting 0 to 20 mA and 4 mA to 20 mA input ranges.
- Fail-safe performance: Performance level PLe according to ISO 13849-1, Category 4, and SIL 3 according to IEC 61508.
- Supply and encoder support: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder supply is 24 V with 300 mA maximum total current of all encoders/channels.
- Installation and protection: Horizontal installation supports -30 °C to 60 °C, with +70 °C for 10 minutes under OT1, ST1/ST2 according to EN 50155. The module has conformal coating and IP? protection is not stated.
Applications
- Rail vehicles: The module supports railway applications including EMC for rail vehicles and rail-vehicle temperature, vibration and shock requirements.
- Stationary industrial systems: The module supports use in stationary industrial systems with resistance classifications according to EN 60721-3-3.
- Industrial process technology: The module supports industrial process technology with environmental classifications according to EN 60654-4 and ANSI/ISA-71.04.
Technical Summary
| Product model | 6AG2136-6AA00-1CA1 |
|---|---|
| Product type | SIPLUS ET 200SP F-AI 4xI 0(4)..20mA 2-/4-wire HF |
| Analog inputs | 4 |
| Input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Supply voltage | 24 V DC; 19.2 V to 28.8 V permissible range |
| Resolution | 16 bit with overrange, including sign |
| Safety classification | PLe, Category 4 according to ISO 13849-1; SIL 3 according to IEC 61508 |
| Firmware | FW update possible; based on 6ES7136-6AA00-0CA1 |
| Mounting temperature | Horizontal: -30 °C to 60 °C; +70 °C for 10 minutes under OT1, ST1/ST2 according to EN 50155 |
| Lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this SIPLUS ET 200SP module?
Confirm the complete order number 6AG2136-6AA00-1CA1 on the nameplate.
Which analog input ranges does 6AG2136-6AA00-1CA1 support?
It supports 0 to 20 mA and 4 mA to 20 mA current input ranges across 4 analog inputs.
Which firmware information is supplied for this module?
FW update is possible, and the module is based on 6ES7136-6AA00-0CA1.
What installation temperature data should be checked?
For horizontal installation, the range is -30 °C to 60 °C, with +70 °C for 10 minutes under OT1, ST1/ST2 according to EN 50155.