Product Description
Key Features
- Digital output configuration: 4 Triac digital outputs with zero point detection, current-sourcing capability, and 2 A rated output current per channel.
- Output capacity: Switching capacity is 2 A maximum with resistive load and 100 W maximum on lamp load; total current is 8 A maximum per module.
- Supply and output voltage: Rated AC supply voltage is 230 V, with a permissible range from 20.4 V to 264 V. Output voltage is 24 V AC to 230 V AC.
- Installation and mounting limits: For horizontal installation, maximum total current is 8 A up to 40 °C, 6 A up to 50 °C, and 4 A up to 60 °C. For vertical installation, it is 8 A up to 30 °C, 6 A up to 40 °C, and 4 A up to 50 °C.
- Firmware and BaseUnit: Firmware version is V1.0, firmware update is possible, and usable BaseUnit is BU type B1. The module has a green/red DIAG LED and green channel-status LED.
Applications
- Digital input control: The module can control a digital input.
Technical Summary
| Product type designation | DQ 4×24 … 230 V AC/2 A ST |
|---|---|
| Product lifecycle | Active Product |
| Digital outputs | 4; Triac with zero point detection |
| Rated AC supply voltage | 230 V |
| Permissible AC supply voltage range | 20.4 V to 264 V |
| Rated output current | 2 A per channel |
| Total current per module, max. | 8 A |
| Usable BaseUnit | BU type B1 |
| Firmware version | V1.0 |
| PROFINET GSD version | GSDML V2.3 |
| Color code | CC41 |
Frequently Asked Questions
What output configuration does 6ES7132-6FD00-0BB1 have?
It has 4 Triac digital outputs with zero point detection, a 2 A rated output current per channel, and 24 V AC to 230 V AC output voltage.
Which BaseUnit and firmware are specified for this module?
The usable BaseUnit is BU type B1. Firmware version is V1.0, and firmware update is possible.
Is short-circuit protection included?
It is without short-circuit protection. When using BU type B1, a miniature, quick-response fuse with 10 A tripping current must be provided.