Product Description
Key Features
- Product identity: SIPLUS S7-1200 SM 1223, DI 16×24 V DC, DQ 16x relay; based on 6ES7223-1PL32-0XB0.
- Digital inputs: 16 digital inputs, 24 V DC rated value, sink/source, in groups of 2; input characteristic curve according to IEC 61131, type 1.
- Relay outputs: 16 relay outputs with 24 V DC relay-coil supply; 2 A rated output current and 2 A maximum switching capacity with resistive load.
- Environmental variant: Conformal coating; ambient temperature during operation -25 °C to 60 °C, with +70 °C for 10 minutes under OT1, ST1/ST2 conditions according to EN 50155.
- Installation and protection: Rail mounting, required front connector, IP20 degree of protection, and 70 mm x 100 mm x 75 mm dimensions.
Technical Summary
| Product type | SIPLUS S7-1200 SM 1223, DI 16×24 V DC, DQ 16x relay |
|---|---|
| Order number | 6AG2223-1PL32-1XB0 |
| Based on | 6ES7223-1PL32-0XB0 |
| Digital inputs | 16; 24 V DC rated value; in groups of 2 |
| Relay outputs | 16; 24 V DC relay-coil supply |
| Output current | 2 A rated value; 2 A permissible maximum for signal "1" |
| Supply voltage | 24 V DC rated value; permissible range 20.4 V to 28.8 V |
| Operating temperature | -25 °C to 60 °C; +70 °C for 10 minutes under OT1, ST1/ST2 conditions according to EN 50155 |
| Conformal coating | Yes; Class 2 for high reliability according to EN 61086 |
Frequently Asked Questions
What exact product identity should be confirmed for this module?
Confirm Siemens 6AG2223-1PL32-1XB0, SIPLUS S7-1200 SM 1223, DI 16×24 V DC, DQ 16x relay, based on 6ES7223-1PL32-0XB0.
How many digital inputs and relay outputs does it have?
It has 16 digital inputs and 16 relay outputs. The inputs are in groups of 2, and the outputs are in groups of 4.
What supply and output values should be checked?
The rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V. Relay output current is 2 A rated and 2 A maximum for signal "1".
What environmental conditions are specified?
Operating temperature is -25 °C to 60 °C, with +70 °C for 10 minutes under OT1, ST1/ST2 conditions according to EN 50155. The module has conformal coating and IP20 protection.