Product Description
Key Features
- Digital output configuration: DQ 16x24VDC/0.5A HF digital output module with 16 current-sourcing transistor outputs in groups of 8.
- Output capacity: Output current is 0.5 A per channel, 4 A per group, and 8 A per module; resistive-load switching capacity is 0.5 A max.
- Supply and output voltage: Rated supply voltage is 24 V DC with a permissible range of 19.2 V to 28.8 V; rated output voltage is 24 V DC.
- Diagnostics and substitute values: The module has single-channel diagnostics, supply-voltage, wire-break, short-circuit, and group-error diagnostics, plus connectable substitute values.
- Environmental configuration: SIPLUS configuration with conformal coating, -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes).
- Installation and firmware: The module is based on 6ES7522-1BH01-0AB0, supports possible firmware updates, and provides rail-based installation.
Technical Summary
| Product type | DQ 16x24VDC/0.5A HF |
|---|---|
| Digital outputs | 16 transistor outputs |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Output current | 0.5 A per channel; 4 A per group; 8 A per module |
| Short-circuit protection | Yes; clocked electronically |
| Diagnostics | Single-channel, wire-break, short-circuit, supply-voltage, and group-error diagnostics |
| Conformal coating | Yes |
| Temperature | -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes) |
| Based on | 6ES7522-1BH01-0AB0 |
| Firmware update possible | Yes |
| Lifecycle | Active Product |
Frequently Asked Questions
What exact module configuration should be confirmed for 6AG2522-1BH01-4AB0?
Confirm the DQ 16x24VDC/0.5A HF designation, 16 transistor outputs, 24 V DC supply, and the installed SIPLUS configuration.
What output current does this module provide?
The output current is 0.5 A per channel, 4 A per group, and 8 A per module.
What diagnostics are available?
Single-channel diagnostics, supply-voltage monitoring, wire-break and short-circuit diagnostics, group-error diagnostics, diagnostic alarms, and maintenance interrupts are available.
What environmental data should be checked?
Check the conformal-coating configuration, -40…+70 °C range, and OT4 with ST1/2 (+85 °C for 10 minutes).