Product Description
Key Features
- Digital output configuration: 4 digital source outputs (PNP, current-sourcing), rated at 24 V DC and 2 A per channel.
- SIMATIC ET 200SP identity: Product type designation: DQ 4×24 V DC/2 A ST; suitable BaseUnit: BU type A0; color code: CC02.
- Output protection and diagnostics: Electronic short-circuit protection, open-circuit detection, supply-voltage monitoring, wire-break and short-circuit diagnostics, group error, and diagnostic alarm.
- Firmware and engineering: Firmware version V1.1.5; firmware update possible. STEP 7 TIA Portal is configurable/integrated from V11 SP2 / V13.
- Connection and installation: 1-wire and 2-wire connections use BU type A0; 3-wire connection uses BU type A0 with AUX terminals or a potential distributor module; 4-wire connection uses BU type A0 + potential distributor module.
- Support lifecycle data: Product lifecycle: Start of final year of support.
Applications
- Digital input control: The outputs can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Technical Summary
| Product type designation | DQ 4×24 V DC/2 A ST |
|---|---|
| Digital outputs | 4 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply-voltage range | 19.2 V to 28.8 V DC |
| Rated output current per channel | 2 A |
| Maximum total current per module | 8 A |
| Suitable BaseUnit | BU type A0 |
| Firmware version | V1.1.5 |
| PROFINET GSDML | V2.3 |
| Protection and diagnostics | Electronic short-circuit protection; open-circuit detection; supply-voltage, wire-break, short-circuit and group-error diagnostics |
| Product lifecycle | Start of final year of support |
Frequently Asked Questions
What order number should be confirmed for this module?
Confirm the complete order number 6ES7132-6BD20-0BA0.
Which BaseUnit and connection variants are supported?
1-wire and 2-wire connections use BU type A0. A 3-wire connection uses BU type A0 with AUX terminals or a potential distributor module. A 4-wire connection uses BU type A0 + potential distributor module.
What firmware version does the module have?
Firmware version is V1.1.5, and a firmware update is possible.
Does the configuration include a potential distributor module?
It is without a potential distributor module; the source lists it for the 3-wire and 4-wire connection variants.