Product Description
Key Features
- Exact module identity: Product type designation: AI 8xI 2-/4-wire BA. The module has Color code CC01 and is suitable for BU type A0, A1.
- Analog current inputs: 8 single-ended analog inputs support current measurement. Input ranges are 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Supply and encoder output: Rated supply voltage: 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder supply is 24 V with short-circuit protection.
- Resolution and conversion: Resolution with overrange: 16 bit including sign. Cycle time for all channels: 1 ms per channel; integration time is parameterizable.
- Diagnostics and installation: The module has diagnostic alarms, supply-voltage monitoring, wire-break detection at 4 to 20 mA, short-circuit detection, Group error and Overflow/Underflow diagnostics. It supports horizontal installation from -30 °C to 60 °C and vertical installation from -30 °C to 50 °C.
- Firmware and engineering: Firmware version: V2.0.0, with FW update possible. Engineering is configurable/integrated from TIA Portal V21 and STEP 7 V5.7 SP3; PROFINET uses GSDML V2.45.
Applications
- Current measurement: Supports current measurement with 2-wire and 4-wire transducers; voltage measurement is not supported.
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Product type designation | AI 8xI 2-/4-wire BA |
| Firmware version | V2.0.0 |
| Analog inputs | 8; Single-ended |
| Current input ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Resolution with overrange | 16 bit including sign |
| Cycle time | 1 ms; per channel |
| usable BaseUnits | BU type A0, A1 |
Frequently Asked Questions
What is the exact product type for Siemens 6ES7134-6GF00-0AA1?
The product type designation is AI 8xI 2-/4-wire BA.
How many analog inputs does this module have?
It has 8 single-ended analog inputs for current measurement.
Which BaseUnits are usable for this module?
BU type A0 and A1 are usable. For 4-wire connections, the source specifies BU type A0, A1 + potential distributor module.
Which firmware version should be confirmed for an installed module?
Firmware version is V2.0.0, and a firmware update is possible.
What configuration details should be confirmed for a legacy-part request?
Confirm the nameplate order number, firmware version, installed BaseUnit, connection variant, quantity, destination and condition preference.