Product Description
Key Features
- Exact module identity: SIMATIC DP ET 200S electronics module, standard I-2-wire, with 4 analog inputs for 2-wire transducers.
- Analog input capacity: 4 analog current inputs support 4 mA to 20 mA into 25 Ohm; cycle time for all channels is max. 40 ms (33 to 40 ms).
- Resolution and measurement: Integrating measurement principle with max. 13 bit resolution including sign; integration time is parameterizable at 16,67 / 20 ms.
- Supply and protection: Rated load voltage L+ is 24 V from the power module, with reverse polarity protection. Transmitter supply is present and short-circuit proof at approx. 200 mA for the module.
- Diagnostics and isolation: SF red LED indicates group error; wire-break diagnosis is available for the 1 to 5 V measuring range only. Channels are isolated from the backplane bus.
- Physical variant and lifecycle: The module is 15 mm wide, 81 mm high and 52 mm deep, with approx. 40 g weight. Product lifecycle: Product cancellation.
Applications
- Current measurement: Current measurement as a 2-wire transducer is supported.
Technical Summary
| Product function | Isochronous mode: No |
|---|---|
| Analog inputs | 4; 4 mA to 20 mA into 25 Ohm |
| Resolution with overrange | 13 bit including sign; 4 to 20 mA: 13 bit |
| Cycle time, all channels | Max. 40 ms; 33 to 40 ms |
| Load voltage L+ | Rated value (DC): 24 V; from power module |
| Input current from load voltage L+, max. | 125 mA without load |
| Input current from backplane bus 3.3 V DC, max. | 10 mA |
| Potential separation | Between channels and backplane bus: Yes; between channels: No |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What order number should be confirmed for this module?
Confirm the complete order number 6ES7134-4GD00-0AB0 on the nameplate or installed-part documentation.
Which input configuration does 6ES7134-4GD00-0AB0 have?
It has 4 analog current inputs for 2-wire transducers, with a 4 mA to 20 mA input range into 25 Ohm.
What supply and mounting dimensions should be checked?
Check the 24 V rated load voltage from the power module and the 15 mm width, 81 mm height and 52 mm depth.
What lifecycle data is supplied for this configuration?
Its product lifecycle is Product cancellation.