Product Description
Key Features
- Exact CPU identity: SIPLUS S7-300 CPU 313C-2DP, based on 6ES7313-6CG04-0AB0.
- Digital I/O and counters: 16 digital inputs, 16 digital outputs, 3 counters with a maximum counting frequency of 30 kHz, and 3 pulse outputs with pulse width modulation up to 2.5 kHz.
- Communication interfaces: Integrated MPI interface and integrated PROFIBUS DP interface; the PROFIBUS DP interface supports master and device operation.
- Supply and memory: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V. Integrated work memory: 128 kbyte; plug-in MMC load memory is supported.
- Environmental variant: Conformal coating with a temperature range of -25…+70 °C.
- Front connection and requirement: One 40-pole front connector; a Micro Memory Card is required.
Applications
- Frequency measurement: The integrated counters support frequency measurement with 3 frequency meters up to 30 kHz.
- PID control: The integrated function blocks support a PID controller.
- Pulse-width modulation: The pulse outputs support pulse width modulation up to 2.5 kHz.
Technical Summary
| Order number | 6AG1313-6CG04-7AB0 |
|---|---|
| Product type | CPU 313C-2DP |
| Based on | 6ES7313-6CG04-0AB0 |
| Supply voltage, rated | 24 V DC |
| Supply voltage, permissible range | 19.2 V to 28.8 V |
| Digital inputs | 16 |
| Digital outputs | 16 |
| Work memory | 128 kbyte |
| Interfaces | MPI; PROFIBUS DP |
| Counting frequency, max. | 30 kHz |
| Temperature range | -25…+70 °C |
Frequently Asked Questions
What CPU type does Siemens 6AG1313-6CG04-7AB0 use?
It uses the CPU 313C-2DP product type and is based on 6ES7313-6CG04-0AB0.
What I/O configuration should be confirmed for this model?
The configuration has 16 digital inputs and 16 digital outputs, with 3 counters and 3 pulse outputs.
Which memory and card requirements should be checked?
The CPU has 128 kbyte integrated work memory, supports plug-in MMC load memory, and requires a Micro Memory Card.
Which interfaces and supply voltage should be matched?
Confirm the integrated MPI and PROFIBUS DP interfaces and the 24 V DC supply range of 19.2 V to 28.8 V.
What lifecycle information is recorded for this configuration?
Product cancellation is recorded for the configuration; confirm the requested quantity, destination and condition preference.